Fort
Rp 1,474,358
Fort 900ERL-2 - EARTH LEAKAGE PROTECTION RELAYS
Fort 900ERL-2 - EARTH LEAKAGE PROTECTION RELAYS - Price (Rp) - FORT-900ERL-2
| Weight | kg |
|---|---|
| Dimensions | |
| Color | |
| Description | Digital Earth Leakage Relay > Input connection : 3Φ/4Wire, 3Φ/3Wire, 1Φ/2wire > Operating Voltage : 230VAC / 110VAC > Output contact : 2 x 1 C/O (SPDT) rating : NO/5A, NC/3A, 250VAC > Trip setting : • Leakage current : 10mA - 30A • Pre alarm : 50 - 100% of leakage current setting > Trip time setting : • Power On Delay : 0.5 - 99.9s • Trip time delay : 0 - 99.9s • Recovery time delay : 0 - 99.9s • Response time : < 30ms (if trip current ≥ 5 x set value) < 50ms (if trip current ≥ 1 x set value) > Accuracy : • Current : ±5% of setting 2 digits • Time delays : ±5% of setting ±100ms > Size : 35 X 90mm |
| Function | • Protection earth leakage current • Leakage current monitoring in 1Φ and 3Φ system • True RMS meansurement • CBCT connection monitoring • Power ON delay • Trip time delay • Recovery time delay • Adjustable switching hysteresis • Test and reset via front / remote • Two separate alarm relays with NC/NC |
| Type | 900ERL-2 |